Key Words: Impluse tester, Hipot Tester, Megger, Load bank

USA Tel:(816) 666-7843

E-Nanny Electric Automation Co., Ltd.

DBMPT-X Touch screen On-site voltage transformer test set

Products overview: DBMPT-X Voltage transformer Field tester was developed with high-end testing technology, large-scale electronic circuit design and accord with national related protocol . It has solved the of big working intensity,trival operation on-site test of current transformer, voltage transformer. Meanwhile the product has a reliable performance,and the function is strong.

Download

Description

Technical indicators:

Test range6kV/100V,10kV/100v,20kV/100V,35kV/100V,6kV/ /100V/ ,10kV/ /100v/ ,20kV/ /100V/ ,35kV/ /100V/ ,66kV/ /100V/ ,110kV/ /100v/ ,220kV/ /100V/    
Tested voltage transformer work scope80%~120%
Second load0.0VA~300VA ,COSφ=0.1~1.0
Be tested voltage transformer accuracy range1.0,0.5,0.2,0.1
Resistance, admittance measurement errors≤5.0%
Measurement range R: 0.00Ω~5.0ΩY:  0.000mS~200.0mS
Basic errorIn-phase component:X=±(X×2%+Y×2%)±2words                            Y=±(X×2%+Y×2%×34.38)±5words                        “X”,“Y”—— display value of Instrument                 “5words”—— quantizing error of InstrumentBatches: grade 1Measurement range:f:0.0000%~200.0%δ:0.000′~999.9 Rated voltage: 100/3V,100/ V,100V
Power consumption20VA
Accuracy level:0.05 S level 
Shape dimension(mm)460(L)*350(W)*40(H)
Weight (kg)10


Product features:

 

Convenient for field conduct on-site verification work

On-site verification voltage transformer do not need Standard voltage transformer,Booster device,Load cases or Pressure adjustable control box,using highly simple test wiring and operation realize the verification of the assolenoid style voltage transformer,greatly reduced the working intensity and improve work efficiency,convenient for field in transformer site verification

Their accuracy for a 0.02,accurate measure the be tested voltage transformer. Then according to the test results of  impedance and admittance to calculated the transformer error

Measuring range is wide,it can measure between  6kV/100V and 220kV/ /100V/

Has the dc resistance and voltage load box test function

Adopt 640 * 480 high-resolution LCD display,with the human interface and operation design,use touch screen auxiliary  operation,make operation more convenient, fast

Adopt an intelligent outside wiring condition judgment,clew wrong wiring, polar error, etc

Automatic to turn the test data in the whole,and determine whether outoftolerance,Outoftolerance data using reverse black  display,the data characteristics of transformer directly and clear

Mass storage can store field test data up to 1,000 bar,with printers,on-site print test data

Adopt the engineering plastic mould chassis that could shockproof,prevent pressure, guarantee operator safety and  equipment safety on the locale high-voltage test


Inquiry

Contact Us

Tel: +86 27 8700 2568

CHN Mob: (86) 135 5447 1180

USA Mob: (816) 666-7843

Email: enannypower@gmail.com

Skype: e-nannypower

WhatsApp: +86 135 5447 1180

WeChat: +86 135 5447 1180

Follow Us