Key Words: Impluse tester, Hipot Tester, Megger, Load bank
USA Tel:(816) 666-7843
Products overview: DBMPT-X Voltage transformer Field tester was developed with high-end testing technology, large-scale electronic circuit design and accord with national related protocol . It has solved the of big working intensity,trival operation on-site test of current transformer, voltage transformer. Meanwhile the product has a reliable performance,and the function is strong.
Description
Technical indicators:
Test range | 6kV/100V,10kV/100v,20kV/100V,35kV/100V,6kV/ /100V/ ,10kV/ /100v/ ,20kV/ /100V/ ,35kV/ /100V/ ,66kV/ /100V/ ,110kV/ /100v/ ,220kV/ /100V/ |
Tested voltage transformer work scope | 80%~120% |
Second load | 0.0VA~300VA ,COSφ=0.1~1.0 |
Be tested voltage transformer accuracy range | 1.0,0.5,0.2,0.1 |
Resistance, admittance measurement errors | ≤5.0% |
Measurement range | R: 0.00Ω~5.0ΩY: 0.000mS~200.0mS |
Basic error | In-phase component:X=±(X×2%+Y×2%)±2words Y=±(X×2%+Y×2%×34.38)±5words “X”,“Y”—— display value of Instrument “5words”—— quantizing error of InstrumentBatches: grade 1Measurement range:f:0.0000%~200.0%δ:0.000′~999.9 Rated voltage: 100/3V,100/ V,100V |
Power consumption | 20VA |
Accuracy level: | 0.05 S level |
Shape dimension(mm) | 460(L)*350(W)*40(H) |
Weight (kg) | 10 |
Product features:
Convenient for field conduct on-site verification work
On-site verification voltage transformer do not need Standard voltage transformer,Booster device,Load cases or Pressure adjustable control box,using highly simple test wiring and operation realize the verification of the assolenoid style voltage transformer,greatly reduced the working intensity and improve work efficiency,convenient for field in transformer site verification
Their accuracy for a 0.02,accurate measure the be tested voltage transformer. Then according to the test results of impedance and admittance to calculated the transformer error
Measuring range is wide,it can measure between 6kV/100V and 220kV/ /100V/
Has the dc resistance and voltage load box test function
Adopt 640 * 480 high-resolution LCD display,with the human interface and operation design,use touch screen auxiliary operation,make operation more convenient, fast
Adopt an intelligent outside wiring condition judgment,clew wrong wiring, polar error, etc
Automatic to turn the test data in the whole,and determine whether outoftolerance,Outoftolerance data using reverse black display,the data characteristics of transformer directly and clear
Mass storage can store field test data up to 1,000 bar,with printers,on-site print test data
Adopt the engineering plastic mould chassis that could shockproof,prevent pressure, guarantee operator safety and equipment safety on the locale high-voltage test