Key Words: Impluse tester, Hipot Tester, Megger, Load bank
USA Tel:(816) 666-7843
DBYZ-301 Automatic Zinc Oxide Lightning Arrester Characteristic Tester is the special equipment of testing zinc oxide arrester electric performance. It is suitable for testing various voltage levels zinc oxide with electricity or without, thus to detect dangerous problems inside the device caused by wet insulation or valve plate aging.
Description
Features:
1. 800 × 480 LCD touch screen,high speed thermal printer;
2. Long distance wireless transmission.PT signal wireless transmission distance more than 400 m, up to 2000 m;
3. Suitable for testing in various situation such as lightning arrester with or without electricity,laboratory;
4. Test three phase current,three pahse voltage at the same time,more efficient;
5. No strong electricity inside,voltage no more than 12V.Current and voltage sensors are completely isolated,safe and reliable;
6. Support various voltage sampling:1. Wired 2 wireless 3. no voltage
A. wire: digital signals transmission with cable which the signal is from PT metering winding;
B. wireless: digital signals wireless transmission which the signal is from PT metering winding;
C. No voltage: No need to get signal from PT terminals.Use software calculation to get voltage standard.
7.Built-in high energy Li-battery.With 6000mAh high energy Li-battery,suitable for no power supply field;
8. Equipped with industrial grade operating system, support direct shutdown mode; With a USB interface,can connect with a USB mouse, keyboard, easy to operate;
9. With a 4GB SD card,can store massive testing datas;
10. Advanced data processing.Supporting upper management software, with functions of historical data management, data analysis,report automatic generation and printing;
11. High speed sampling frequency, advanced digital signal processing technology, strong anti-interference performance, high precision measurement results;
12. With dustproof, waterproof, anti-corrosion plastic sealed box, small size, light weight, easy to carry.
Specification:
Power Supply: 220V, 50Hz or internal battery;
Measuring range:
Leakage Current (RMS) 0-10mA (scalable);
Voltage (RMS) 30-100V (scalable).
Measuring accuracy:
Current: total current> 100μA, ± 2% of reading ± 1 digit;
Voltage: Voltage signal> 30V, ± 2% of reading ± 1 digit.
Wireless Accuracy: 5%
Measurement parameters:
Leakage current total current waveform, fundamental wave RMS, peak value.
Resistive component fundamental wave RMS of leakage current, 3,5,7 times RMS.
Resistive component peak value of leakage current,Including positive peak value Ir+,negative peak value Ir-.
Capacitive current fundamental wave, full voltage, full current phase angle difference.
Voltage RMS.
Lightning arrester power.
Voltage datum signal sampling method:
Sync with cable: 40 meters (can be extended)
Wireless sync:> 400 meters (can be extended);
Battery parameter:
Charging time> 6 hours
Continuous working time> 4 hours
Continuous working hours> 8 hours;
Dimension: 34cm × 22cm × 20cm;