Key Words: Impluse tester, Hipot Tester, Megger, Load bank

USA Tel:(816) 666-7843

E-Nanny Electric Automation Co., Ltd.

DBM-9580 Gas Chromatograph Analyzer

DBM-9580 Gas Chromatograph Analyzer is to analyze the gas content of insulation oil by gas chromatographic method. 

Download

Description

Product Introduction

DBM-9580 Gas Chromatograph Analyzer is to analyze the gas content of insulation oil by gas chromatographic method. It is effective to judge if the running equipment has potential fault like over-heat, discharge or not, to ensure the safety of power grid. It is also necessary to be used for manufacturer of gas/oil equipment to inspect their equipment before leaving factory.

The gas is considered as carrier gas. When sample gas is sent to sample injector,it will enter into packed column or capillary column by carrier gas. As the boiling point, polarity and adsorption coefficient of each components of sample gas are different, the components will be separate, then the detector behind will detect each components in sequence according to physicochemical characteristic. At last, the chromatographic analyzer will record and analyze the chromatogram of each components and get the results.


Product Features

1. 5.7-inch color LCD screen, meets the demands of different users.

2. Using advanced 10/100M adaptive Ethernet communication interface, and built-in IP protocol stack, realizing long distance data transmission easily through intranet and internet.

3. Design of 3 independent connection process. It can be connected with local processing(laboratory), more convenient for supervisors to monitor running status and analyze the results.

4. Equipped with network edition workstation, simultaneously support multiple chromatograph working, with data processing and control, which simplifies the document management, and reduce the lab investment cost and running cost.

5. System in English and Chinese, which can be switched freely.

6. Using a multiprocessor parallel working mode, more stable and reliable. It meets complex sample analysis, FID and TCD detector are supplied. Other detector can be optional if necessary.

7. One piece TCD detector and 2pcs FID detectors are supplied, including H2 and O2 are detected by TCD detector, hydrocarbon gas such as methane, ethylene, ethane, acetylene are detected by FID1 detector, CO and CO2 are detected by FID2 detector.

8. Brand-new microcomputer temperature control system,high precision and reliability. 6-channels independent temperature control system, 16steps temperature programmed, broad range sample analysis. It also has automatic door system to improve the LV temperature accuracy and faster temperature speed.

9. Modular design, clear and convenient to upgrade system.

10. With timing and self-starting program, easily complete online analysis of gas sample.(It is necessary to select online sample components by users.)

11. Full computer keyboard operation system, simple operation, more convenient. Detectors have automatic identification technology. It also has fault diagnosis and power-off data protection function, automatic memory setting parameters.

12. Built-in low noise, high resolution 24digit AD circuit, and functions of baseline storage/deduction.

13. Suitable for using in WinXP, Win2000, Windows7 operation system. Standard CDF file will be read for sampling data, so it can be integrated with Agilent, Waters chromatographic work station.

14. With MODBUS/TCP standard port, easy to connect with DCS.

15. It can be integrated with automatic sampler produced by various manufacturer, such as Shimadzu AOC-20i, HTA HT series liquid/gas sampler.


Technical Specifications

1. Temperature control range: room temperature 5-400℃, step 1℃, accuracy ±0.1℃

2. Temperature increasing steps: 16steps.

3. Increasing speed: 0.1-40℃/min

4. Gas control: mechanical valve control mode and electronic pressure flow control mode for option.

5. External event: 4channels.

6. Sampler type: packed column, capillary tube, six-way valve gas sampling, automatic headspace sampling for option.

7. Detector: FID, TCD, ECD(optional), FPD(optional)

8. Start mode: automatic or manual.

9. Communication port: Ethernet, IEEE802.3


FID(flame ionization detector)

● Detection limit: ≤2×10-11g/s (Hexadecane/isooctane)

● Baseline noise: ≤5×10-14A

● Baseline shift: ≤1×10-13A/30min

● Linear range: ≥ 106


TCD(thermal conductivity detector)

● Sensitivity: S≥2500mV•ml/mg (benzene/methylbenzene) (enlarge 1,2,4,8 times for option)

● Baseline noise: ≤20μV

● Baseline shift: ≤30μV/30min

● Linear range: ≥104


ECD (electron capture detector) optional

● Detection limit: 1×10-13g/ml (Hexachlorocyclohexane/isooctane)

● Baseline noise: ≤0.03mV

● Baseline shift: ≤0.2mV/30min

● Linear range: 103

● Radioactive souce: 63Ni


FPD (flame photometric detector) optional

● Detection limit: (S)≤5×10-11g/s, (P)≤1×10-12g/s(parathion-methyl/ absolute ethyl alcohol)

● Baseline noise:≤3×10-13A

● Baseline shift: ≤2×10-12A/30min

● Linear range: sulphur≥102, phosphorus≥103

Inquiry

Contact Us

Tel: +86 27 8700 2568

CHN Mob: (86) 135 5447 1180

USA Mob: (816) 666-7843

Email: enannypower@gmail.com

Skype: e-nannypower

WhatsApp: +86 135 5447 1180

WeChat: +86 135 5447 1180

Follow Us