Key Words: Impluse tester, Hipot Tester, Megger, Load bank

USA Tel:(816) 666-7843

E-Nanny Electric Automation Co., Ltd.

DBM-8000 Automatic Capacitance and Tan-Delta Test Set

DBM-8000 Automatic Capacitance and Tan-Delta Test Set is designed to measure dissipation ( Dielectric Loss  factor/DF/tgδ) or power factor (PF/cosφ )

Download

Description

Product Introduction

DBM-8000 Automatic Capacitance and Tan-Delta Test Set is designed to measure dissipation ( Dielectric Loss  factor/DF/tgδ) or power factor (PF/cosφ ) in heavy electromagnetic interference environment such as in power plants or substations. Also it can be used in laboratory for high accurate test. 


The test set is all-in-one structure: including precision digital bridge, 12kV/200mA frequency conversion power unit, reference capacitor (CN), and other electronic circuits. An external power supply can expand the test range. True portability is realized by the light weight. Simple usage is realized by the full automation. High per¬formance is realized by the digital process.


Product Features

1. DBM-8000 has advanced interference suppression circuit based on the frequency conversion and digital filter technique, the ratio of interference current to specimen current is 2:1(200%). 
2. High speed A/D converters, processed by a DSP. self-calibrating, accuracy standard capacitor, so the DBM-8000 has high accuracy. All the input resistance is less than 2 Ohm, the attached capacitance of connection cable is negligible. Not only for on-the-spot test, it can also be used in laboratory for high accuracy test, such as oil dissipation factor test.
3. Safe protection: output protection, input protection, grounded protection, fault protection. 
4. DBM-8000 has multiple functions:UST / GST /GSTg, all these functions with internal high voltage power supply need no assistant equipment. Using an external high voltage power supplies over 12kV or 5A. All test work will be done automatically after start the set.
5. The set can save 100 groups of data. And has a serial port to transmit data to the computer.


Technical Specifications

  Specifications
Accuracy
Cx:                                   ±(reading×1%+1pF)
DF tgδ:                           ±(reading×1%+0.00040)
PF cosφ:                        ±(reading×1%+0.00040)
Interference
 Ratio of interference: current to specimen current is 2:1 (   200% )
Capacitance Range
Internal HV 3pF~60000pF / 10kV,  60pF~1uF/0.5kV
External HV
 3pF~1.5uF/10kV
Resolution
 0.001pF, 4 digitals
No limit, Resolution
0.001%
tgδ Range
 (C/L/R specimen is automatic recognized)
Input current range
10μA~5A
Internal HV
0.5~12kV / 200mA (max)
Accuracy
±(reading×1%+10V)
Control mode
Rise or fall smoothly
Frequency
 45Hz, 50Hz, 55Hz, 60Hz,65Hz single frequency
45Hz/55Hz, 55Hz/65Hz,47.5Hz/52.5Hz dual   frequency
External HV
UST: 5A max; GST: 12kV/5A max, 38-72Hz
Test Time
30s typical may vary in different test mode
Power Supply
95V~130V,180V~260V,50Hz/60Hz or 1phase power supply or generator
Display
128*64 dot matrix
Printer
Thermal printer
Operating Temperature
-10℃~50℃
Storage Temperature
-20℃~60℃
Humidity
<90% non-condensing



Inquiry

Contact Us

Tel: +86 27 8700 2568

CHN Mob: (86) 135 5447 1180

USA Mob: (816) 666-7843

Email: enannypower@gmail.com

Skype: e-nannypower

WhatsApp: +86 135 5447 1180

WeChat: +86 135 5447 1180

Follow Us